ProPointPlus Aspirating Smoke Detectors

 

  • 1-4Individual detectors per aspirator (providing up to 4 separately identifiable areas)

  • High performance optical ‘Scatter Chamber Detectors’ (SCD)

             (or)

  • High performance optical ‘Scatter Chamber Detectors’ (SCD) and enhanced CO detection

  • Multiple language, multi-function LCD display

  • Simple install and commission process without the need for a laptop connection

  • Simple Class A, Class B, Class C and Prison sensitivity configuration set up

  • Inbuilt algorithm to avoid unwanted alarms

  • Airflow monitoring per pipe

 

 

Description

ProPointPlus Optical ‘Smoke’ and ‘Smoke/CO’ detection 

Aspirating detection is now a recognised solution for many different fire detection applications. ProPointPlus provides up to four separate detectors within a common aspirator enclosure and therefore provides four individually identifiable areas of detection per aspirator.

Each of the four plug-in ‘Scatter Chamber Detectors’ (SCD)’s detector modules can be either ‘optical’ only or combined.

‘optical/enhanced CO’ detectors for small single room applications. Independent and integrated alarm decision making through the use of complex algorithms extend the range of particle detection, confirm genuine alarms and reduce unwanted alarms.

Installation, configuration and commissioning of ProPointPlus detectors is very simple and installer friendly.

Configuration to either Class A, Class B or Class C sensitivity options is achieved through a multi-language, multi-function LCD display without the need for a laptop connection.

Detector set up allows the installer to configure the detector sensitivity to exactly the same equivalent as a known number of point type smoke detectors for each Class A, Class B and Class C system. This ensures the system specifier, designer, installer and commissioning engineer configure the ProPointPlus SCD’s to the correct sensitivity for the particular application.

Aspirator fan speed and airflow configuration is a also a very simple process allowing ProPointPlus aspirating detectors to be installed in a variety of applications with short and relatively long pipe runs.

Technical

Supply Voltage

21 - 29VDC

Power Consumption

9.6 watts quiescent
(24VDC 100% Fan Speed)

Current Consumption

300mA with blower @ 30%
400mA with blower @ 100%

Operating Conditions
Detector Ambient

0˚C to 38˚C (32˚F to 100˚F)

Operating Conditions
Tested to

0˚C to 55˚C (32˚F to 131˚F)

Operating Conditions
Sampled Air

-20˚C to 60˚C (-4˚F to 140˚F)

Operating Conditions
Humidity 

10 - 95%RH, non-condensing

IP Rating

 IP30

Cable Access

10 x 20mm knock outs

Cable Termination

Screw terminal blocks
(0.2 - 2.5mm2, 30 - 12AWG)

Sampling Network

Four inlet ports with combined sampling pipe length up to 200m (750ft) subject to  ’ProFlow’ sampling pipe calculation program. Maximum transport time = 120 seconds.

Pipe ID

19mm to 25mm (preferred OD 25mm)

Alarm Indications

Pre-alarm warning and Fire per pipe

Other Indications

Supply Healthy, General Fault

Programmable Inputs

3 monitored inputs that may be configured for Isolate, Reset, Silence, Battery Fault and Mains Fault

Programmable Output Relays

5 Relays rated 1A @ 30VDC
(Volt-free change over contacts)

Event Log / Data Retention

24,000 events stored on FIFO basis
(alarms, actions, faults and data points)
(Approx 30 day historical graph data)

EN54 Approved Sensitivity Settings

Optical only SCD
Class A - 3 holes per detector (per pipe)
Class B - 5holes per detector (per pipe)
Class C - 12holes per detector (per pipe)

Optical/Enhanced Heat SCD
Class A - 3 holes per detector (per pipe)
Class B - 5holes per detector (per pipe)
Class C - 8holes per detector (per pipe)

Airflow Monitoring

‘High Airflow’ and ‘Low Airflow’ fault monitoring

Weight

3kg (6.6lbs)

Dimensions (mm)

380(H) x 250(W) x 137(D)

Product Approval

CoCP No: 0359-CPR-00476
DoP No: PFD-CPR-0107
Relevant Standard: EN54 Part 17 & 20
AS7240 Part 20

 

15LHK1529-01

 

 

 

 

 

Diagram

Other

Application Guide

Class A - High Sensitivity Applications include:- Small Computer Rooms, Cleanrooms, Data Centres, Control Rooms, Archive Storage & EDP areas

Class B - Enhanced Sensitivity Applications include:- Small Historic Buildings, Museums, Theatres, Galleries, High Ceiling Areas, Small Clean Warehouses & Small Atria Areas

Class C - Normal Sensitivity and Harsh Environment Applications include:- Lift/Elevator Shafts, Small Cold Storage Facilities, Clean Warehouses, Atria, Inaccessible Voids & Up to 4 x separately identifiable Prison Cells per aspirator.