ProPointPlus Aspirating Smoke Detectors
-
1-4Individual detectors per aspirator (providing up to 4 separately identifiable areas)
-
High performance optical ‘Scatter Chamber Detectors’ (SCD)
(or)
-
High performance optical ‘Scatter Chamber Detectors’ (SCD) and enhanced CO detection
-
Multiple language, multi-function LCD display
-
Simple install and commission process without the need for a laptop connection
-
Simple Class A, Class B, Class C and Prison sensitivity configuration set up
-
Inbuilt algorithm to avoid unwanted alarms
-
Airflow monitoring per pipe
Description
ProPointPlus Optical ‘Smoke’ and ‘Smoke/CO’ detection
Aspirating detection is now a recognised solution for many different fire detection applications. ProPointPlus provides up to four separate detectors within a common aspirator enclosure and therefore provides four individually identifiable areas of detection per aspirator.
Each of the four plug-in ‘Scatter Chamber Detectors’ (SCD)’s detector modules can be either ‘optical’ only or combined.
‘optical/enhanced CO’ detectors for small single room applications. Independent and integrated alarm decision making through the use of complex algorithms extend the range of particle detection, confirm genuine alarms and reduce unwanted alarms.
Installation, configuration and commissioning of ProPointPlus detectors is very simple and installer friendly.
Configuration to either Class A, Class B or Class C sensitivity options is achieved through a multi-language, multi-function LCD display without the need for a laptop connection.
Detector set up allows the installer to configure the detector sensitivity to exactly the same equivalent as a known number of point type smoke detectors for each Class A, Class B and Class C system. This ensures the system specifier, designer, installer and commissioning engineer configure the ProPointPlus SCD’s to the correct sensitivity for the particular application.
Aspirator fan speed and airflow configuration is a also a very simple process allowing ProPointPlus aspirating detectors to be installed in a variety of applications with short and relatively long pipe runs.
Technical
Supply Voltage |
21 - 29VDC |
Power Consumption |
9.6 watts quiescent |
Current Consumption |
300mA with blower @ 30% |
Operating Conditions |
0˚C to 38˚C (32˚F to 100˚F) |
Operating Conditions |
0˚C to 55˚C (32˚F to 131˚F) |
Operating Conditions |
-20˚C to 60˚C (-4˚F to 140˚F) |
Operating Conditions |
10 - 95%RH, non-condensing |
IP Rating |
IP30 |
Cable Access |
10 x 20mm knock outs |
Cable Termination |
Screw terminal blocks |
Sampling Network |
Four inlet ports with combined sampling pipe length up to 200m (750ft) subject to ’ProFlow’ sampling pipe calculation program. Maximum transport time = 120 seconds. |
Pipe ID |
19mm to 25mm (preferred OD 25mm) |
Alarm Indications |
Pre-alarm warning and Fire per pipe |
Other Indications |
Supply Healthy, General Fault |
Programmable Inputs |
3 monitored inputs that may be configured for Isolate, Reset, Silence, Battery Fault and Mains Fault |
Programmable Output Relays |
5 Relays rated 1A @ 30VDC |
Event Log / Data Retention |
24,000 events stored on FIFO basis |
EN54 Approved Sensitivity Settings |
Optical only SCD Optical/Enhanced Heat SCD |
Airflow Monitoring |
‘High Airflow’ and ‘Low Airflow’ fault monitoring |
Weight |
3kg (6.6lbs) |
Dimensions (mm) |
380(H) x 250(W) x 137(D) |
Product Approval |
CoCP No: 0359-CPR-00476 |
15LHK1529-01 |
|
Other
Application Guide
Class A - High Sensitivity Applications include:- Small Computer Rooms, Cleanrooms, Data Centres, Control Rooms, Archive Storage & EDP areas
Class B - Enhanced Sensitivity Applications include:- Small Historic Buildings, Museums, Theatres, Galleries, High Ceiling Areas, Small Clean Warehouses & Small Atria Areas
Class C - Normal Sensitivity and Harsh Environment Applications include:- Lift/Elevator Shafts, Small Cold Storage Facilities, Clean Warehouses, Atria, Inaccessible Voids & Up to 4 x separately identifiable Prison Cells per aspirator.