6000PLUS/HT/SVAD

 

  • Ideal where Smoke Detection is Unsuitable

  • Integrated Electronic Sounder

  • Integrated EN54-23 Visual Alarm Device

  • Loop Powered

  • Low Current

  • Programmable Volume Control

  • Integral Short Circuit Isolator

  • FAST™ Addressing

  • VAD Classification Adjustable from 3m to 7.5m Room Coverage Volume

 

Description

The Protec Algo-Tec™ 6000PLUS sensor range has been developed to incorporate advanced fire sensing technology, electronic sounders, high intensity LED visual alarm devices (VAD) and speech enhanced talking sounder capability, all integrated within the sensor head and powered from the loop.

6000PLUS/HT/SVAD
Interactive addressable heat sensor with low thermal mass thermistor, giving fast response to temperature increases.

The intelligent sensor data is evaluated by the Protec Algo-Tec™ 6000PLUS interactive programmable algorithms.
Suitable for applications where smoke detection is unsuitable but require a high sensitivity heat detector. Examples are boiler rooms, kitchens, laundries and ventilated areas.

Sensor Sounder - The above Protec Algo-Tec™ 6000PLUS/HT/SVAD sensor is equipped with an integrated loop powered electronic sounder with three programmable sounder tone options, constant, pulse or warble selectable by the control panel along with adjustable volume control. A loop short circuit isolator is also incorporated within the head. The sensor sounder tones are compatible with the full range of Protec 6000 electronic sounders.

Sensor VAD - Compliance with DDA legislation is assisted by the addition of the Protec visual alarm device (VAD) to the 6000PLUSensor, to warn those with hearing impairments or in noisy environments. The VAD utilises a high intensity LED with lower power consumption and increased reliability when compared to alternative indicators.
The VAD is located in the centre of the sensor, so can be viewed from all angles.
Suitable for ceiling mounting the VAD distributes light in a cylindrical pattern to achieve the required minimum illumination of 0.4lux over the entire coverage area in accordance with EN54-23.
The maximum mounting height is 3m with a coverage diameter of 7.5m.
For smaller areas the device can be programmed on-site for coverage diameter of 3m or 5m at reduced power.

Technical

Environment

-10°C to +50°C (95% R.H. non condensing)

Ingress Protection

IP21C

Weight (excluding base)

108.6g

Loop Powered

Yes

Loop Voltage

18 - 28V

Loop Standby Load

0.55mA

Peak Alarm Load

24mA

Mounting Height

3m

Coverage

7.5m, 5m or 3m cylindrical diameter

VAD Flash Rate

1Hz or 0.5Hz white flash

Isolator

Yes

Device Protocol

Algo-Tec™ 6000PLUS

Dimensions (mm)

95ø x 54.5H

Product Approval

CoCP No: 0356-CPR-0407
Dop No: PFD-CPR-0085
Relevant Standard: EN54 Part 3, 5, 17 &23
AS7240 Part 5 & 23
CE Marked

Diagram

Other

Tone Options

Warble Tone: 990Hz(250ms), 730Hz(250ms)
Continuous Tone: 990Hz
Pulse Tone: 990Hz(500ms), Silence(500ms)
 

Tone Volume Options

The tone and volume are selectable at the control panel (measured at one metre):
High: 85dB(A), Mid: 75dB(A), Low: 65dB(A)
 

BASE Options

6000PLUS/BASE
- Low profile common mounting base

6000PLUS/FFBASE
- Fast fixing semi recessed base


Note - base options above are included in the product approval.

 

15LHK0958-01