6000/MCP

 

  • Unique Installation Concept

  • Anti-Tamper Facility

  • Enhanced Aesthetics

  • Fully Approved to the Latest Standards

  • Re-settable Break Glass Element

  • Backward Compatibility

 

 

 

Description

Installation efficiency, flexibility and full compliance with the latest standards are at the heart of the 6000/MCP indoor call point.

Installation time and ultimately cost, are of paramount importance to any fire or security installer.

The 6000/MCP range directly reflects this need by providing a simple connection concept designed specifically to reduce installation time.

The 6000/MCP utilises a special terminal block, where all initial installation cabling is terminated. This terminal block is then simply connected to the back of the 6000/MCP. Simple, but effective, with no re-termination required and no time wasted.

The 6000/MCP indoor call point also helps to preserve the integrity of the overall system, as illegal removal of the product lid will result in the call point operating and the system going into alarm.

Full compliance with the latest standards is essential and the 6000/MCP indoor call point is fully approved to the latest EN54 Part 11 standard.

Technical

Environment

-10°C to +55°C

Humidity

0-95% non condensing

Ingress Protection

IP24D

Weight (excluding base)

Flush - 93g, Surface - 144g

Operating Voltage

16 - 30V DC

Loop Powered

Yes

Loop Standby Load

450μA

Loop Alarm Load

0.85mA

LED Illuminated

4.5mA

Dimensions (mm)

89(W) x 93(H) x 27.5(D)

Device Protocol

Algo-Tec™ 6000

Product Approval

LPCB Certificate No: 201ae/01
EC Certificate No: 0832-CPD-1049
Dop No:
PFD-CPR-0018 (UK Model)

PFD-CPR-0019 (Dutch Model)
PFD-CPR-0020 (Export Model)
Relevant Standard: EN 54-11 & 17
CE Marked
AS7240 Part 11 (Export Model only)

Diagram

MCP Typical Wiring Diagram

Other

 
LPCB ref. no. 201ae/01