6000/MICCO

 

  • Protec Algo-Tec™ 6000 Protocol

  • Loop Powered

  • Monitored Input Interface

  • Clean Contact Output Interface

  • Integral Short Circuit Isolator

  • Optional Delayed Input Mode

  • Optional Non Latching Alarm Mode

 

 

Description

The Protec 6000 series MICCO is a loop powered fault monitored input and a volt free clean contact output interface. An on board isolator is provided which protects against loop short circuits on either the incoming or outgoing loop connections.

Under normal circumstances the input is terminated with an End of Line resistor. If the correct value of resistance is placed across the monitored input, theMICCO will activate the associated 6000 control panel within 3 seconds. A PCB link may be removed which will delay a sustained activation by 14 seconds, designed for use when interfacing to sprinkler systems. The input is fully monitored for open and short circuit wiring faults.

 

Technical

Environment

-10°C to +50°C (95% R.H. non condensing)

Ingress Protection

IP41

Weight (excluding base)

109g

Loop Powered

Yes

Loop Standby Load

0.55mA (Average), 2mA (Peak)

Loop Alarm Load

2.2mA (Average), 5mA (Peak)

Loop Voltage

16 - 28V

Isolator

Yes

Inputs

Input monitored for short / open circuit fault and alarm

Outputs

Single pole changeover rated for 5A maximum at 230V AC (non inductive)

Dimensions (mm)

86.7(H) x 147.3(W) x 10(D)

Device Protocol

Algo-Tec™ 6000PLUS

Relevant Standard

EN-17 & 18, CE Marked

Diagram

Wiring Diagram

Micco Wiring Diagram