6000/APZA
-
Easy to Use
-
Reduce Installation Cost
-
Simple Expansion Using Existing Wiring
-
FAST™ Addressing
-
Integral Short Circuit Isolator
-
Auxiliary 24V dc Powered
-
Protec Conventional Detector and Call Point Zone
-
Built in Sounder Circuit Monitored for Open / Short Circuit Faults
Description
This interface is ideally suited for small conventional fire detection to be fully integrated with Protec Intelligent addressable systems. The 6000/APZA is powered using an external EN54 Part 4 power supply. It can support up to 20 Protec conventional (3000PLUS) detectors.
The zone end of line is selectable using the on board DIL switch and can be programmed to resistive or capacitive as per the requirement of BS5939-1. The sounder circuit is monitored for open and short circuit faults and has 1A current drive capability.
The interface has an inbuilt loop short circuit isolator fitted as standard.
Technical
Loop Protocol |
Protec Algo-tec 6000™ |
Loop Isolator |
Yes |
Loop Voltage |
18 to 28V peak loop |
Number of Addresses |
1 |
24V Auxiliary Voltage |
18 to 28V dc |
Environment |
-10 to 50°C (maximum 95% RH no condensation or icing) |
Loop Quiescent Current |
0.6mA |
Loop Alarm Current |
0.6mA |
Auxiliary 24V Current |
0.6mA Quiescent + detector load ( 13mA max ) + resistive end of line load ( 3mA ) |
Zone Circuit EOL² |
Resistive - 8.2Ω ±5% ¼W Capacitive - 100µF ±20% in series with 22Ω ±5% ¼W |
Manual Call Point |
Must be fitted with a 330Ω or 180Ω series resistor |
Detectors Supported |
Protec 3000 and 3000PLUS |
Sounders Supported |
Protec 3000 series |
Sounder Circuit EOL² |
10kΩ ±5% ¼W |
Sounder Circuit Current |
1A |
Weight |
120g |
Indications |
On-board red indicating LED showing when the device is polled, or in the alarm state |
Product Approval |
BSI Kitemark No: KM589455 |
Note: EOL = End of Line