6000/2LPZA
-
-
2x Monitored Detection Zones
-
2x Monitored Alarm Outputs
-
Loop Powered
-
DIN Rail Mounted
-
Integral Short Circuit Isolator
-
Protec Algo-Tec 6000 Protocol
-
Description
The Protec 2 way loop zone alarm interface is a loop powered input / output device providing 2 local zones of conventional detectors and 2 local monitored alarm outputs.
Technical
Loop protocol |
Protec Algo-tec™ 6000 MX1 |
Loop isolator fitted |
Yes, on board (consult Protec DEL2110 for details) |
Loop voltage range |
18 to 28V peak loop |
Number of loop addresses used |
2 maximum, user and build configurable |
24V Auxiliary input voltage range |
18 to 28V dc |
Environmental operational limits |
-10 to 50ºC (maximum 95% RH no condensation or icing) |
Loop quiescent current (24V loop peak) |
1.6mA + zone end of line current + zone loading |
Loop alarm current (average) |
18mA |
Zone short circuit current (24V) |
26mA peak ± 2mA |
Zone end of line requirements (I/P 1 & I/P 2) |
Resistive - 8.2k ±5% ¼W, Capacitive - 100μ F ±20% in series with 22Ω ±5% ¼W |
Input cabling requirements |
Maximum cable resistance 6Ω per conductor |
Monitored input end of line details |
End of line resistor value 47kΩ 1/4W ±5% |
Monitored input short circuit threshold |
Below 230Ω |
Monitored input fire threshold |
Below 7.85kΩ |
Monitored input pre-alarm threshold |
Below 32kΩ ( Input 3 only ) |
Monitored input open circuit threshold |
Above 111kΩ |
Clean contact output details |
1 Single pole changeover rated for 2A maximum at 24V dc ( non inductive ) |
Weight |
245g ( including din rail housing, no backbox, 4 way build ) |
LED Indicator |
Use only high brightness LED (Protec stock code: NK 02-676-46) |