Cirrus Pro 100
-
Cloud Chamber Detection Principle
-
Up to 100 mtrs Sampling Pipe
-
Programmable ‘Pre-Alarm’ warning condition
-
3 Programmable ‘Fire’ warning conditions
-
Silence and Reset Buttons
-
Vast Sensitivity Range
-
Latching / non latching alarm contacts
-
Airflow Monitoring
-
‘Fault Diagnostic’ feature
-
Immune to dust, humidity & temperature changes
-
UL/FM Approved
Description
The new range of Cirrus Pro Series Aspirating Fire Detectors provide a solution for almost any aspirating system project, from a simple single pipe detector with minimum ‘Fire’ and ‘Fault’ LED indications to a multiple pipe scanning detector with multifunction quarter VGA backlit LCD display. Programming for each detector is via a laptop computer or from an onboard or remotely mounted LCD display.
The Cirrus Pro 100
- ‘Cloud Chamber’ aspirating fire detector
- For use with up to a total of 100mtrs of 25mm diameter sampling pipe.
- Single sampling pipe ‘inlet’ port, single sampling pipe ‘exhaust’ port.
- LED status indication of Common Fault, Power, Pre-alarm, Fire 1, Fire 2, Fire 3 alarm conditions
- Internal buzzer ‘Silence’ button, detector alarm ‘Reset’ Button.
- May be networked with other Cirrus Pro Series aspirating detectors
Technical
Supply Voltage |
20 - 29VDC |
Power Consumption |
7.2 watts quiescent (24VDC 90% Fan Speed) |
Current Consumption |
350mA quiescent 50mA alarm (24VDC 90% Fan Speed) |
Dimensions (mm) |
285(W) x 215(H) x 144(D) |
Weight |
4kg (8.8lbs) |
Operating Conditions |
0°C to 38°C (32°F to 100°F) |
Operating Conditions |
0°C to 55°C (32°F to 131°F) |
Operating Conditions |
-20°C to 60°C (-4°F to 140°F) |
Operating Conditions |
10 - 95%RH, non-condensing |
IP Rating |
IP30 |
Cable Access |
6 x 20mm knock outs |
Cable Termination |
Screw terminal blocks |
Sampling Network |
Single inlet port with combined sampling pipe length up to 100m typically (325ft.) Maximum Transport Time allowed up to 120 seconds. |
Pipe ID |
19 to 25mm (preferred OD 25mm) |
Alarm Indications |
Pre-alarm, Fire 1, Fire 2, Fire 3. |
Other Indications |
Supply Healthy, General Fault. |
Sensitivity Range |
20,000 particles per cc to 3 million particles per cc 10 programmable sensitivity ranges. |
Programmable Inputs |
4 monitored inputs that may be configured for Isolate, Reset, Disable, Fault, Gain Set, Battery Fault and Mains Fault, Silence and Reset button, Disable. |
Programmable Output Relays |
5 Relays rated 1A @ 30VDC |
Event Log |
128 events stored on FIFO basis. |
Data Retention |
Approx 10 day historical graph |
Variable Sensitivity Settings |
7 day programmable settings with 3 time zones per day. |
Airflow Monitoring Adjustable |
‘High Airflow’ and ‘Low Airflow’ fault monitoring. |