Cirrus Pro 200DSC
-
-
-
Cloud Chamber Detection Principle
-
Upto 200 mtrs Sampling Pipe
-
Programmable ‘Pre-Alarm’ warning condition
-
3 Programmable ‘Fire’ warning conditions
-
Multi-function Display and Programmer
-
‘Alarm’ action text
-
Vast Sensitivity Range (incipient to conflagrating)
-
Latching / non latching alarm contacts
-
Airflow Monitoring
-
‘Fault Diagnostic’ feature
-
Immune to dust, humidity & temperaturechanges
-
UL/FM Approved
-
-
Description
The new range of Cirrus Pro Series Aspirating Fire Detectors provide a solution for almost any aspirating system project, from a simple single pipe detector with minimum ‘Fire’ and ‘Fault’ LED indications to a multiple pipe scanning detector with multifunction quarter VGA backlit LCD display. Programming for each detector is via a laptop computer or from an onboard or remotely mounted LCD display.
The Cirrus Pro 200DSC
- Cloud Chamber’ aspirating fire detector
- For use with up to a total of 200mtrs of 25mm diameter sampling pipe.
- Four ‘individually identifiable’ sampling pipe ‘inlet’ ports, single sampling pipe ‘exhaust’ port.
- LED status indication of Common Fault, Power, Pre-alarm, Fire 1, Fire 2, Fire 3 alarm conditions
- Internal buzzer ‘Silence’ button, detector alarm ‘Reset’ Button.
- Multifunction Quarter VGA back lit LCD and programmer.
- May be networked with other Cirrus Pro Series aspirating detectors
Technical
Supply Voltage |
20 - 29VDC |
Power Consumption |
14 watts in alarm |
Current Consumption |
550mA quiescent 700mA alarm |
Dimensions (mm) |
440(W) x 385(H) x 144(D) |
Weight |
9kg (19.8lbs) |
Operating Conditions |
0°C to 38°C (32°F to 100°F) |
Operating Conditions |
0°C to 55°C (32°F to 131°F) |
Operating Conditions |
-20°C to 60°C (-4°F to 140°F) |
Operating Conditions |
10 - 95%RH, non-condensing |
IP Rating |
IP30 |
Cable Access |
20 x 20mm knock outs |
Cable Termination |
Screw terminal blocks |
Sampling Network |
Four inlet ports with combined sampling pipe length up to 200m (650ft.) MaximumTransport Time allowed up to |
Pipe ID |
19 to 25mm (preferred OD 25mm) |
Sensitivity Range |
20,000 particles per cc to 3 million particles per cc 10 programmable sensitivity ranges. |
Alarm Indications | Pipe 1: Pre-alarm, Fire 1, Fire 2, Fire 3 Pipe 2: Pre-alarm, Fire 1, Fire 2, Fire 3 Pipe 3: Pre-alarm, Fire 1, Fire 2, Fire 3 Pipe 4: Pre-alarm, Fire 1, Fire 2, Fire 3 |
Other Indications |
Supply Healthy, General Fault. |
Sensitivity Range |
20,000 particles per cc to 3 million particles per cc 10 programmable sensitivity ranges. |
Programmable Inputs |
4 monitored inputs that may be configured for Isolate, Reset, Disable, Fault, Gain Set, Battery Fault and Mains Fault. |
Programmable Output Relays |
17 Relays rated 1A @ 30VDC |
Event Log |
128 events stored on FIFO basis. |
Data Retention |
Approx 10 day historical graph |
Variable Sensitivity |
7 day programmable settings with 3 time zones per day |
Multi-function Display |
Cirrus Pro 200DSC incorporates a quarter VGA backlit LCD. In normal conditions the Date, Time, Detector Text and Particle Levels are all displayed. Alternatively any Fault, Pre-Alarm or Fire conditions will be displayed. Event Logs, ‘Historical’ and ‘Real Time’ graphs may also be displayed. |
Airflow Monitoring |
‘High Airflow’ and ‘Low Airflow’ fault monitoring. |