3000/FIREBEAM40
-
Infra-Red Transmitter and Receiver
-
Technician Friendly
-
Simple Menu System
-
Low Power Usage
-
Cost Effective
Description
At ground level the controller unit is used to make operational adjustments. The standard unit covers a range of 5 to 40 metres. To increase the beam range additional reflectors are added.We have 2 kits available; FIREBEAM40/80KIT for a range of 40 to 80 metres, and FIREBEAM80/100KIT for a range of 80 to 100 metres.
The Protec 3000/FIREBEAM40 is conventional device and is compatible with the Protec 3000 range.
The 3000/FIREBEAM40 head incorporates microprocessor controlled motors that intelligently align the head at all times. When first commissioned the head accurately aligns itself, and in operation the head will re-align should there be building movement, a problem with new build settlement and environmental change. The units unique ability to self align means that high level re-adjustment because of this, is no longer required, saving time, disruption and cost. The motorised head means greater reliability that will reduce troublesome false alarms.
Maintenance is also simplified as the low level controller has a simple menu system viewed through an LCD screen. All adjustments can be made at ground level including a test procedure and full diagnostics.
Technical
onstruction |
Housing: white high heat abs UL94 HB |
Ingress Protection |
IP65 |
Environment |
-10ºC to 55ºC (10 to 95% R.H. non condensing) |
Weight |
Approx: Head 1Kg / Controller 0.5Kg |
Dimensions (mm) |
Beam Head - 155(W) x 180(H) x 137(D) |
Time to Fault |
Adjustable between 2s to 60s |
Time to Fire |
Adjustable between 2s to 30s |
Sensitivity |
Fully adjustable between 25% to 50% |
Supply Voltage |
12V dc to 24Vdc +25% -15% |
Quiescent Current |
3mA |
Alarm Current |
3mA |
Aligning Current |
3mA |
Fault/Fire Relay Contact Rating |
2A @ 30Vdc |
Relevant Standard |
EN54 & AS7240 Part 12 |